_____________Cruise control for your pump!
1. Variable Speed Capability.
With a VFD it is possible vary the speed of any standard, off the shelf three
phase motor
from full off to full on RPM. This feature along with the Integral Controls
Pump Station (ICPS) control unit allows a pump to run at whatever speed needed
to deliver the desired flow rate and/or pressure. At partial pump capacity there's
no "slam on/slam off" operation and no over-pressure conditions as
may be the case with constant speed pumps. When started the motor smoothly "ramps
up" and quickly "zeros in" on the target pressure. An alternate
target pressure can be selected and changed "on the fly" when higher
or lower pressures are needed.
One example using alternate pressures is a golf course/housing development water
system that would run at a target pressure of 50-60 PSI to service the relatively
low volume water needs of the surrounding houses. A signal from the sprinkler
controller selects a target pressure of 100 PSI to provide adequate pressure
for the golf course sprinklers to be maintained only when they turn on for a
few hours at night. When the sprinkler cycle is complete the pressure returns
to the normal 50-60 PSI target pressure.
This selectable target pressure feature is very helpful for systems where water
drains out of the lines after the pump has stopped. Air then gets into the lines
and restarting a conventional pump "across the line" at full speed
generates extremely high (and sometimes destructive) pressures. With the ICPS
control system the pump can started at a very low pressure and after a time
sufficient to fill the lines automatically switch to the higher pressure for
normal operation.
2. Single phase to three phase conversion.
VFD's provide single phase to three phase conversion as a part of the speed
control process and it expected that VFD's will obsolete phase converters in
the not-too-distant future. To use single phase power simply connect the voltage
source wires to the L1 and L2 terminals on the VFD. To use three phase power
connect the input voltage wires to L1, L2 and L3. The output (load) voltage
is always three phase regardless of the input voltage source.
3. Significant cost/electrical equipment savings using a VFD with single phase
power.
Using a VFD makes it possible to use three phase equipment with single phase
power. Considerable savings can be realized when using deep well submersible
pumps:
A. The single phase submersible pump control box with start and run capacitors
and switchover equipment is eliminated and a starter/contactor is not needed.
B. The three phase output from single phase voltage allows smaller wire sizes
over long runs.
For example a 900 foot deep 5 HP submersible pump using single phase power would
require #2 copper wire. For three phase operation from a VFD #6 wire can be
used - a savings of
nearly $2.00 per foot in wire alone ($1800.00)! The full load amperage for the
5 HP pump is
reduced from 23.0 amps with the single phase system to 16.6 amps with the three
phase system.
C. Three phase motors are typically more widely available and less expensive
than their equivalent single-phase counterparts.
D. VFD's are even available to provide 240 volt three phase from 120 volt single
phase power.
4. Significant cost/equipment savings using a VFD for nearly any pump.
The VFD replaces the pump panel and monitors nearly 100 electrical parameters.
All that's needed is a circuit breaker or set of fuses so the power can be shut
off. With VFD operation there's no need for pressure reducing or pressure relief
valves, numerous bladder tanks and a large pump house big enough to contain
all of that equipment. The "ramp up" and "ramp down" speed
can be adjusted to eliminate any surges and a small bladder tank will adequately
service even a very large water system since the bladder tank is needed only
for cushion, not for storage.
5. More cost savings: "Hybrid" VFD + on-off pump capability.
Multiple ICPS control units with one managing the VFD and the others controlling
the on-off pumps provide the net effect of VFD operation at a small fraction
of the cost of an all-VFD system. Typically a small HP VFD (read: low cost)
is used to perform most of the pumping chores while the on-off pumps smoothly
"cut in" and "cut out" as needed to maintain the desired
pressure and flow rate.
6. Significant cost/power savings with VFD controlled partial-speed operation.
With an electric motor the power required increases at a cube of the shaft speed.
That means if the motor speed (motor RPM) is reduced by 20% the power requirements
are reduced over 50%. To put it another way if the motor is operated at 80%
of full speed the motor requires only 1/2 of the electric power (wattage) it
would need at full speed.
Valve regulated systems run the pump motor at full speed and then, if the pressure
is too high for a given flow rate "burn off" unneeded energy using
friction provided by the pressure regulating valve (PRV). Any pressure rise
upstream of the PRV represents wasted electrical energy. Conversely A VFD controlled
system simply doesn't put the energy into the motor in the first place. VFD
power usage compared to constant speed valve regulated operation can be up to
40% less depending on flow requirements and other factors.
For more detailed information on how power usage is calculated please see our
application note: Power Requirements: Valve regulation vs. Speed regulation.
7. VFD's are readily available for most every application.
VFD's are available from ½ HP to 250 HP and with voltage ranges from
110 to 575 volts and all will accept single phase input power. That covers most
every conventional pumping application.
8. Significant cost savings Period.
Like most electronic equipment nowadays (computers, VCR's etc.) the cost is
going down, not up. The ICPS control unit also provides low pressure safety
shutoff protection and all components "plug in" to make upgrades or
modifications quick and easy.
Return to Main Page